Quantité minimale : 1
| Product ID | P11373 |
| IO-Link-Specifications | revision 1.1, baud rate COM 2, min. cycle time 5 ms, process data 8 byte |
| Protection [EN 60529] | IP 54 |
| Material housing | PBT |
| Compressive strength | 16 bar |
| Temperature monitoring | 0 ... 60 °C |
| Medium temperature | 0 ... 60 °C |
| Electrical connection | M12 connector |
| Material sensor touched by medium | ceramic, stainless steel, PA, aluminum |
| Accessories | mounting plate 72 x 63 x 3 |
| Ambient temperature | 0 ... 60 °C |
| Process connection | G1/4 |
| Output | IO-Link, analog output 4…20 mA, linear, switching output NO/NC PNP/NPN, pulse output PNP/NPN NO |
| Start-up time | 4 ... 12 s |
| Load RL | 200 ... 500 Ω |
| TYPE | LDN 1009 GAPL |
| Measurement error | flow ± (4 % of measurement value + 0.5 % of end value) / temperature ± 2 °C |
| Detection range compressed air (Nl/min) | 0,5...250 Nl/min |
| Switching current max. | 150 mA |
| Detection range compressed air (Nm³/h) | 0,04 ...15 Nm³/h |
| Process data flow | 0...1500 [Nm³ x 0,01] |
| Process data temperature | 0...600 [°C x 0,1] |
| Process data consumption pressured air | 0...999999 x 10⁶ [Nm³ x 0.01] |
| Current consumption max. | 70 mA |
| Supply voltage | 18 ... 30 VDC |
| Medium | air |
| Note | * reference 1013 mbar / 20 °C |
| Reaction time | < 0,3 s |
| Programmable functions | switching point, access code, NC/NO, analog range, impulse, min/max memory, average value |