Quantité minimale : 2
Product ID | P31445 |
IECEx marking dust | Ex ia IIIC T₂₀₀80 °C Da |
Ambient temperature dust in zone 20 | -25 ... 75 °C |
Maximum values | Ui = 12.6 V / Ii=15.9 mA / Pi = 50 mW / Ci = 66.2 nF / Li = 1.2 mH |
UKEX Certificate | EPS 22 UKEX 1 139 X |
Protection [EN 60529] | IP 67 |
Ambient temperature gas zone 0 T6 | -25 ... 75 °C |
Ambient temperature gas zone 0 T5 | -25 ... 75 °C |
Material housing | brass-Ni, PA |
ATEX Certificate | EPS 17 ATEX 1 173 X |
Ambient temperature gas zone 0 T4 | -25 ... 75 °C |
Ambient temperature gas zone 0 T3 | -25 ... 75 °C |
Thread/sleeve | M12x1 |
IECEx Certificate | IECEx EPS 17.0087X |
ATEX marking gas | Ex II 1G Ex ia IIC T6...T3 Ga |
Ex area uf use | Zone 1, Zone 0, Zone 20, Zone 21 |
Electrical connection | 2 m PVC-cable 2x0,5 mm² |
Operating Distance sn | 2 mm flush |
ATEX Marking dust | Ex II 1D Ex ia IIIC T₂₀₀80 °C Da |
IECEx marking gas | Ex ia IIC T6...T3 Ga |
Note | with longer cable available on request |
TYPE | IGEXa 02 |